| Galaxy VS | 400V |
| Topology | On-line double conversion |
| Nominal power (kW) | 10-150 kW(parallel up to 600 kW)[4 UPSs in parallel] |
| Key features | |
| Scalability option | 50-150 kW |
| N+1 redundancy option | 20-50 KW N+1 |
| Modular elements | Power modules with Live Swap.static switch module.smart battery modules.intelligence module |
| Display | Color touch screen.4.3 inches,status LED.mimic on display |
| High priority for C&l | Network management card included with ethernet (SNMP)and modbus.8 dry contacts (4 inputs,4 outputs) |
| Maintenance bypass | Internal maintenance bypass.Optional maintenance bypass panel |
| Parallel capability | Simplified 1+1 parallel (for redundancy);Up to 4 UPSs in parallel for capacity or redundancy |
| Ffficiency | |
| Double conversion mode | Up to 97% |
| ECO mode | Up to 99% |
| ECOnversion mode | Up to 99% |
| Input | |
| Nominal input voltage | 3807400/415V |
| nput voltage range (phase to phase) | +/-15% |
| Single mains/dual mains | Single mains as standard.Easily converted to dual mains |
| Input frequency | 40-70 Hz |
| nput power factor | EC power factor:>0.99@load>25%,>0.95@load>15% |
| Maximum short-circuit rating | 65 kA |
| Backfeed protection | Included |
| Output | |
| Nominal output voltages | 380/400/415V |
| Load power factor | PF=1 (0.7 leading to 0.7 lagging without derating |
| Voltage regulation | +1-1% |
| Frequency | 50/60 Hz+-0.1%free running |
| Overload | 1 min @150%;10 min @125% |
| Output THDU on linear load | <1% |
| Battery type | VRLA.Lithium-io |
| Nominal battery voltage,UPS for external batteries | 480-576V(at ratings 50 kW.100 kW.150 kW):60 kW:432-576;384-576V(at other ratings,including 60 kW and 120 kW) |
| Nominal battery voltage.UPS with internal batteries | 480VDC |
| Charging power | Charging power in %of output power at 0-40%load:80%:Charging power in %of output power at 100%load:20% |
| Environment | |
| Acoustic noise.UPS for external batteries | 57 dB(70%load)/65dB(100%load) |
| Acoustic noise,UPS with internal batteries | 54-65 dB.depending on load percentage and model |
| Dust protection | Air filter included.Conformal coated boards |
| Seismic | With optional kit.OSHPD tested |
| Environmental | Green Premium Certified.RoHS,Reach |
1. May I take some samples to test before I placing the order? Yes, we can offer sample testing for you to verify product quality and performance. 2. What is the warranty? We support 1 years warranty. 3.What can you buy from us? Eaton, Vertiv, APC, Santak, Vesion & OEM/ODM UPS; Cooling, MDC, PDU and so on. 4. What payment methods does your conmpany support? We could accept T/T, credit card, Alipay or L/C at sight. 5. What are the terms can you offer for us? We could offer EXW, FOB, CIF, DDP and so on.