US$278.57 | 1 Piece (MOQ) |
Functions | online monitoring and recording 1 ~ 3 channel AC leakage current and current, used for circuit insulation fault troubleshooting, monitoring intermittent leakage fault, check the happen time of insulation fault and maintenance lines, etc. |
Power Supply | DC 3.7V rechargeable lithium battery(full charge about 4.2V) |
Test Mode | Clamp CT, true RMS |
Display Mode | LCD128dots×64dots |
Current Clamp | 1-3PCS(Optional) |
Instrument Dimension | Host:78mm×165mm ×42mm Current clamp 030: 115mm ×70mm×33mm |
Weight | Host: 330g Current clamp 030: 170g |
LCD Dimension | Display field:44mm×27mm |
Current Clamp Model | 030 |
Current Clamp Lead Cable | 2 core shield wire, length 2M |
Sampling Rate | 2 times/second |
Data storage | 200,000 groups (Power down or replace battery will not lose the data) |
Record Period | Set the record interval time within 1 second ~ 99 minutes, 0 seconds is not automatically stored. |
Record Time | Interval time 1 seconds, can continues recording 48 hours |
Interval time 10 seconds, can continues recording 120 hours | |
Interval time 1 minute, can continues recording 168 hours | |
Download Speed | 60KB/ Min |
Line Voltage | Below AC600V circuit test |
Overflow Display | Exceed measure range overflow function: ''OL'' symbol display |
Battery Voltage | Use 3.7V rechargeable lithium battery, power energy display with 3-grid, when the power energy is 0-grid indicate battery voltage is low, please charge in time |
Rated Power | In power save mode about 6mA, Max about 35mA |
Communication Interface | USB |
Record Time | In power save mode continues working 7days |
Working Temperature | Working:-1040below 80%rh |
Temperature Error | Below -10or above 40error influence 1% |
Stored Temperature | Storage:-1060below 70%rh |
Insulation Resistance | 100MΩ or larger, 1000V |
Suitable Safety Standard | IEC1010-1, IEC1010-2-032, Pollution Class 2, CAT(600V),IEC61326(EMC standard) |