Parameter | Value |
Applicable grid | Three-phase four-wire, three-phase three-wire, single two-wire, three-phase three-wire PT |
Working power | Voltage range | AC/DC85~265V |
Power consumption
| ≤5W |
Input | Voltage | Rated | AC100V,220V,400V |
Overload | 1.2 times continuous, 2 times (10s) |
Power consumption | <0.4VA/Phase |
Impedance | ≥200kΩ |
Current | Primary current | 1-9999A |
Secondary input | 1A or 5A |
Short-time overcurrent | 20 times the maximum current for 0.5 seconds |
Power consumption | <0.2VA/Phase |
Impedance | ≥0.1Ω |
Frequency | 45Hz~65Hz |
Switching input | Dry contact input, photoelectric isolation |
Output | Switching output | Relay output; can set any alarming power, default remote control |
Pulse output | 1 channel electrical energy pulse |
Accuracy index | Voltage/current | 0.5% |
Frequency | 0.2% |
Power/power factor | 1% |
Active power | Class0.5S |
Reactive power | CLass2 |
Communication | Bus type | RS485 |
protocol | Modbus RTU |
Baud rate | 2400/4800/9600/19200/38400bps |
Address range | 1-247 |
Bus load | 64pcs |
Communication distance | 1000m |
Parity | EVEN/ODD/NONE(default) |
Data bits | 8 |
Stop bit | 1 |
Ethernet por | Modbus |
Environment | Operation temperature | -25ºC~55ºC |
Storage temperature | -40ºC~70ºC |
Operating humidity | ≤90%RH, non-condensing, no corrosive air |
Storage humidity | ≤95%RH, non-condensing, no corrosive air |
Altitude | ≤2000m |
Installation category | CATIII |
Withstanding voltage capacity | AC withstanding voltage 4KV/1min Pulse withstanding voltage 6kV - 1.2µS waveform |
IP Class | IP51(Indoors) |
Insulation class | 2 |
Average trouble-free operation time | ≥50000h |
EMC electromagnetic compatibility test | Electrostatic discharge immunity test | GB/T 17626.2-2006:test level 4, test voltage 8kV |
RF electromagnetic field immunity test | GB/T 17626.3-2006:test level 3, test field strength of 10V / m |
Fast transient pulse group test | GB/T 17626.4-2008:test level 2, current voltage 1kV, other 500V |
Surge (shock) immunity test | GB/T 17626.5-2008:test level 4, test voltage 4kV |
RF field induction conducted harassment immunity test | GB/T 17626.6-2008:test level 3, test field strength of 10V / m |
Voltage transients, short interruptions and voltage changes in the immunity test | GB/T 17626.11-2008:current and voltage test error qualified |
Oscillation wave immunity test | GB/T 17626.12-1998:Class B ITE test, qualified |
Conformity to Standards | GBT22264.1-2008 Mounted digital display electrical measuring instrument Part 1: Definition and general requirements |
GBT22264.7-2008 Mounted digital display electrical measuring instrument Part 7: Special requirements for multifunctional instruments |
GBT22264.8-2009 Mounted digital display electrical measuring instrument Part 8:Recommended test methods |