Product Description
1.Three leg core:Made of grain oriendted low loss electrolami nations insulated on both sides.2.Resilient spacers:To insulate core and windings from mechanical vibrations,resulting in low noise emissions.3.HV winding:Consisting of vacuum potted single foil type aluminum or copper coils.4.LV winding:Made of copper or aluminum strip.Turns firmly glued together by means of insulating sheet wrapper material.5.Insulation:Mixture of epoxy resin and quatrz powder.Makes the transformer maintenance free,moistureproof,tropicalized,flame resistant and self extinguishing.6.Clamping frame and truck:Rollers can be swung around for lengthways or sideways travel.7.LV terminals:Normal arrangement:top,rear.Special version:Bottom,available on request at extra charge.8.HV terminals:Variable arrangerments,for optimal station design.HV tapping links on low voltage side for adjust ment to system conditions,reconnectable in deenergized state. Three Phase Dry Type Transformer Core
The core is beveled and stepped for maximum performance and minimal bulk. After the magnetic steel is produced by the cutting machine, it is continuously cut into specific lengths by the automatic stacking machine, and then automatically stacked. The correct size is ensured during the entire stacking and assembly process to ensure the high quality of the product.
Dry Type Distribution Transformer Winding
The low voltage winding adopts the whole section of copper foil, which is wound on the special low-voltage foil winding machine with the F-grade insulation. The foil coil solves the outstanding problems such as low voltage, high current coil winding, high short-circuit stress, unbalanced ampere turns, poor heat dissipation effect, windingspiral angle, unstable manual welding quality and so on. At the same tim-e, the winding ends of our company aresealed with resin, cured and formed, moisture-proof and antifouling. The lead copper bar is automatically welded byargon arc welding.
Dry Type Power Transformer Accessories
All the accessories you need to customize our products to your needs.
The casing is made from bolts on a steel plate with removable panels for attachment and tape. Depending on the application and your requirements, the surface treatment can be galvanized, painted. The design is optimized to ensure the required cooling of the transformer at all levels of protection. The enclosure can be shipped assembled on the transformer or flat packed for on-site assembly.
Other Accessories
cooling fan.
Temperature monitoring unit (thermal control system)Product Feature
1. Low loss, low noise, low partial discharge.2. Strong anti-short circuit capability and high anti-lightning impact level.3. Excellent moisture resistance for operation at 100% relative humidity.4. Strong overload capability for long-term operation at 150% loading.
Temperature control device:The transformer adopts the BWDK series signal thermometer. The temperature measuring element is embedded in the upper half of the low-voltage coil, which can automatically detect and display the respective working temperature of the phase coil, and has the function of over temperature alarm and trip.
More Product Parameters
SCB10 10kV Epoxy-resin Insulation Dry-type Transformer
Rated Capacity(kVA) | Voltage Combined | Vector-group | No-load Loss(W) | 75ºC Load Loss(W) | No-load current(%) | Short-circuit Impendance(%) |
High voltage(KV) | Tapping Ranges | Low voltage(KV) |
30 | 6 6.3 6.6 10 10.5 11 | ±5% ±2×2.5% | 0.4 | Dyn11 Yyn0 | 190 | 710 | 2.4 | 4 |
50 | 270 | 1000 | 2.4 |
80 | 370 | 1380 | 1.8 |
100 | 400 | 1570 | 1.8 |
125 | 470 | 1850 | 1.6 |
160 | 540 | 2130 | 1.6 |
200 | 620 | 2530 | 1.4 |
250 | 720 | 2760 | 1.4 |
315 | 880 | 3470 | 1.2 |
400 | 980 | 2990 | 1.2 |
500 | 1160 | 4880 | 1.2 |
630 | 1340 | 5880 | 1.0 |
630 | 1300 | 5960 | 1.0 | 6 |
800 | 1520 | 6960 | 1.0 |
1000 | 1770 | 8130 | 1.0 |
1250 | 2090 | 9690 | 1.0 |
1600 | 2450 | 11730 | 1.0 |
2000 | 6050 | 14450 | 0.8 |
2500 | 3600 | 17170 | 0.8 |
1600 | 2450 | 12960 | 1.0 | 8 |
2000 | 3050 | 15960 | 0.8 |
2500 | 3600 | 18890 | 0.8 |
|
SCB1110kV Epoxy-resin Insulation Dry-type Transformer
Rated Capacity(kVA) | Voltage Combined | Vector-group | No-load Loss(W) | 75ºC Load Loss(W) | Short-circuit Impendance(%) | Size(mm) | Track gauge(mm) |
High voltage(KV) | Tapping Ranges | Low voltage(KV) |
30 | 6 10 10.5 11 | ±5% | 0.4 | Dyn11 Yyn0 | 180 | 560 | 4 | 800x660x940 | 400x400 |
50 | 260 | 730 | 830x690x990 | 400x400 |
80 | 320 | 1120 | 860x690x1020 | 400x400 |
100 | 350 | 1370 | 900x720x1060 | 550x550 |
125 | 430 | 1620 | 940x740x1080 | 550x550 |
160 | 480 | 1900 | 1220x770x1100 | 550x550 |
200 | 540 | 2100 | 1240x780x1170 | 550x550 |
250 | 650 | 2560 | 1390x800x1200 | 550x550 |
315 | 760 | 3010 | 1410x820x1230 | 550x550 |
400 | 780 | 3690 | 1500x860x1270 | 660x660 |
500 | 840 | 4300 | 1520x870x1520 | 660x660 |
630 | 1040 | 5160 | 6 | 1600x890x1410 | 660x660 |
800 | 1240 | 6290 | 1660x950x1460 | 820x820 |
1000 | 1430 | 7380 | 1760x970x1500 | 820x820 |
1250 | 1500 | 8830 | 1800x1090x1620 | 820x820 |
1600 | 1710 | 10580 | 1870x1100x1700 | 820x820 |
2000 | 2200 | 12810 | 1980x1180x1800 | 1070x1070 |
2500 | 2650 | 15080 | 2090x1260x1930 | 1070x1070 |
SCB13 10kV Epoxy-resin Insulation Dry-type Transformer
Rated Capacity(kVA) | Voltage Combined | Vector-group | No-load Loss(W) | Load Loss under Different Insulation and Heat Resistance Levels | No-load current(%) | Short-circuit Impendance(%) |
High voltage(KV) | Tapping Ranges | Low voltage(KV) | B(100ºC) | P(120ºC) | H(145ºC) |
30 | 6 6.3 6.6 10 10.5 11 | ±5% ±2×2.5% | 0.4 | Dyn11 Yyn0 | 150 | 670 | 710 | 760 | 2.4 | 4.0 |
50 | 215 | 940 | 1000 | 1070 | 2.4 |
80 | 295 | 1290 | 1380 | 1480 | 1.8 |
100 | 320 | 1480 | 1570 | 1690 | 1.8 |
125 | 375 | 1740 | 1850 | 1980 | 1.6 |
160 | 430 | 2000 | 2130 | 2280 | 1.6 |
200 | 495 | 2370 | 2530 | 2710 | 1.4 |
250 | 575 | 2590 | 2760 | 2960 | 1.4 |
315 | 705 | 3270 | 3470 | 3730 | 1.2 |
400 | 785 | 3750 | 3990 | 4280 | 1.2 |
500 | 930 | 4590 | 4880 | 5230 | 1.2 |
630 | 1070 | 5530 | 5880 | 6290 | 1.0 |
630 | 1040 | 5610 | 5960 | 6400 | 1.0 | 6.0 |
800 | 1215 | 6550 | 6960 | 7460 | 1.0 |
1000 | 1415 | 7650 | 8130 | 8760 | 1.0 |
1250 | 1670 | 9100 | 9690 | 10370 | 1.0 |
1600 | 1960 | 11050 | 11730 | 12580 | 1.0 |
2000 | 2440 | 14450 | 14450 | 15560 | 0.8 |
2500 | 2880 | 17170 | 17170 | 18450 | 0.8 |
SCB14 10kV Epoxy-resin Insulation Dry-type Transformer
Rated Capacity(kVA) | Voltage Combined | Vector-group | No-load Loss(W) | Load Loss under Different Insulation and Heat Resistance Levels | No-load current(%) | Short-circuit Impendance(%) |
High voltage(KV) | Tapping Ranges | Low voltage(KV) | B(100ºC) | P(120ºC) | H(145ºC) |
30 | 6 6.3 6.6 10 10.5 11 | ±5% ±2×2.5% | 0.4 | Dyn11 Yyn0 | 130 | 605 | 640 | 685 | 2.4 | 4.0 |
50 | 185 | 845 | 900 | 965 | 2.4 |
80 | 250 | 1160 | 1240 | 1330 | 1.8 |
100 | 270 | 1330 | 1415 | 1520 | 1.8 |
125 | 320 | 1565 | 1665 | 1780 | 1.6 |
160 | 365 | 1800 | 1915 | 2050 | 1.6 |
200 | 420 | 2135 | 2275 | 2440 | 1.4 |
250 | 490 | 2330 | 2485 | 2665 | 1.4 |
315 | 600 | 2945 | 3125 | 3355 | 1.2 |
400 | 665 | 3375 | 3590 | 3850 | 1.2 |
500 | 790 | 4130 | 4390 | 4705 | 1.2 |
630 | 910 | 4975 | 5290 | 5660 | 1.0 |
630 | 885 | 5050 | 5365 | 5760 | 1.0 | 6.0 |
800 | 1035 | 5895 | 6265 | 6715 | 1.0 |
1000 | 1205 | 6885 | 7315 | 7885 | 1.0 |
1250 | 1420 | 8190 | 8720 | 9335 | 1.0 |
1600 | 1665 | 9945 | 10555 | 11320 | 1.0 |
2000 | 2075 | 12240 | 13005 | 14005 | 0.8 |
2500 | 2450 | 14535 | 15445 | 16605 | 0.8 |
SCB18 10kV Epoxy-resin Insulation Dry-type Transformer
Rated Capacity(kVA) | Voltage Combined | Vector-group | No-load Loss(W) | Load Loss under Different Insulation and Heat Resistance Levels | No-load current(%) | Short-circuit Impendance(%) |
High voltage(KV) | Tapping Ranges | Low voltage(KV) | B(100ºC) | P(120ºC) | H(145ºC) |
30 | 6 6.3 6.6 10 10.5 11 | ±5% ±2×2.5% | 0.4 | Dyn11 Yyn0 | 105 | 605 | 640 | 685 | 2.4 | 4.0 |
50 | 155 | 845 | 900 | 965 | 2.4 |
80 | 210 | 1160 | 1240 | 1330 | 1.8 |
100 | 230 | 1330 | 1415 | 1520 | 1.8 |
125 | 270 | 1565 | 1665 | 1780 | 1.6 |
160 | 310 | 1800 | 1915 | 2050 | 1.6 |
200 | 360 | 2135 | 2275 | 2440 | 1.4 |
250 | 415 | 2330 | 2485 | 2665 | 1.4 |
315 | 510 | 2945 | 3125 | 3355 | 1.2 |
400 | 570 | 3375 | 3590 | 3850 | 1.2 |
500 | 670 | 4130 | 4390 | 4705 | 1.2 |
630 | 775 | 4975 | 5290 | 5660 | 1.0 |
630 | 750 | 5050 | 5365 | 5760 | 1.0 | 6.0 |
800 | 875 | 5895 | 6265 | 6715 | 1.0 |
1000 | 1020 | 6885 | 7315 | 7885 | 1.0 |
1250 | 1205 | 8190 | 8720 | 9335 | 1.0 |
1600 | 1415 | 9945 | 10555 | 11320 | 1.0 |
2000 | 1760 | 12240 | 13002 | 14005 | 0.8 |
2500 | 2080 | 14535 | 15445 | 16605 | 0.8 |
Payment Term
Payment Terms | T/T | EXW | 30% T/T in advance, the balance to be paid before dispatch |
FOB |
CIF | 30% T/T in advance, the balance to be paid against the copy of B/L |
CFR (C&F) |
L/C | Irrevocable L/C at sight could be accepted if amount above US $50,000.00 |
Delivery Time | 7 to 10 working days after receiving advanced payment |
FAQ
Q:what's your major products?
A: oil immersed transformer, dry type transformer, Transformer Substation, High and Low Voltage SwitchgearQ: Can your product be customized?
A: Considering differences in voltage, frequency and other special transformer product in different countries and regions, our product can be customized according to your requirements.Q: When can I get the price?
A:Usually we quote within 24 hours after we get your inquiry.Q: What about lead or shipping time?
A: The lead time depends on the quantity you ordered, generally within 15 days upon receipt of advance payment.Q: What is the price of shipping?
A: Depending upon the port of delivery, prices varies.Q: Do you offer guarantee for the products?
A: Yes. We offer at least one years guarantee for all of our transformers.Q: Your Advantage?
A: 15 years experience, Advanced production equipment, Stable quality, Fast delivery, Professional & good & Prompt service. Also some free parts can be provided for you.
>>
Pulp Paper Making Pump Spare Parts Propellers
>>
The design of the main entrance house is suitable for families with high-grade wooden doors
>>
Steel Structure Expendable Winding Mandrel for Winding Machine
>>
Customized Professional Authentic Bulk Wholesale Ingredients Red Sishi Ginger
>>
China Lift Elevator 1600kg Lifting Capacity Manufacturing Elevator Price Sighteyes Lift Ife
>>
Tempered Glass Computer Case with Argb Fan Controller
>>
Carambola Anti Insect Guava Kraft Paper Bag for Fruit Growing
>>
Unisupply Plastic Food Container Meal Prep Container Takeaway Box with Inner Tray
>>
Wholesale Luxury Chocolate Packaging Box Rigid Chocolate custom logo gift box Valentine Gift Case Candy Box
>>
Woven Brown DOT Stylish Necktie
>>
UFO Industrial Lighting LED High Bay Light for Factory Warehouse Mine
>>
Sports Equipment Accessories PU Handrail for Good Quality
>>
Wondfo Vet Progesterone Test Kit Progestrone Test for Canine Prog Test Finecare Dog Machine Analyzer Supplier
>>
Yinghe Hot and Cold 480mm Laminating Machine
>>
20FT Chemical Industry Transport ISO Tank Container
>>
High Quality Machined Bubble Level with Screw Holes Rb-Sq701516
>>
HC-B020 electrolyte analyzer Serum/Plasma/Whole Blood/Urine/CSF ion detection clinical laboratory equipment
>>
Breathing Fitness Exerciser Vital Capacity Training Breathing Chewing Gum Wyz19433
>>
ASTMD3822 Standard Test Machine For Tensile Properties of Single Textile Fibers
>>
Good Condition Used Cat 320dl Used Excavator Caterpillar 20ton Digger